# $Id$
|
|
#
|
|
# generisches fhem Modul für Geräte mit Modbus-Interface
|
|
# verwendet Modbus.pm als Basismodul für die eigentliche Implementation des Protokolls.
|
|
#
|
|
# This file is part of fhem.
|
|
#
|
|
# Fhem is free software: you can redistribute it and/or modify
|
|
# it under the terms of the GNU General Public License as published by
|
|
# the Free Software Foundation, either version 2 of the License, or
|
|
# (at your option) any later version.
|
|
#
|
|
# Fhem is distributed in the hope that it will be useful,
|
|
# but WITHOUT ANY WARRANTY; without even the implied warranty of
|
|
# MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
|
|
# GNU General Public License for more details.
|
|
#
|
|
# You should have received a copy of the GNU General Public License
|
|
# along with fhem. If not, see <http://www.gnu.org/licenses/>.
|
|
#
|
|
##############################################################################
|
|
# Changelog:
|
|
#
|
|
# 2015-03-09 initial release
|
|
# 2015-07-22 added documentation for new features introduced in the base module 98_Modbus.pm
|
|
# that can be used here.
|
|
# 2016-04-16 Load Modbus base module instead of require - avoids messages when fhem reloads Modbus
|
|
# because a serial Modbus device is defined afterwards
|
|
# 2016-06-18 added documentation for alignTime and enableControlSet (implemented in the base module 98_Modbus.pm)
|
|
# 2016-07-07 added documentatoin for nextOpenDelay
|
|
#
|
|
|
|
package main;
|
|
use strict;
|
|
use warnings;
|
|
|
|
|
|
#####################################
|
|
sub
|
|
ModbusAttr_Initialize($)
|
|
{
|
|
my ($modHash) = @_;
|
|
|
|
#require "$attr{global}{modpath}/FHEM/98_Modbus.pm";
|
|
LoadModule "Modbus";
|
|
require "$attr{global}{modpath}/FHEM/DevIo.pm";
|
|
|
|
ModbusLD_Initialize($modHash); # Generic function of the Modbus module does the rest
|
|
|
|
$modHash->{AttrList} = $modHash->{AttrList} . " " . # Standard Attributes like IODEv etc
|
|
$modHash->{ObjAttrList} . " " . # Attributes to add or overwrite parseInfo definitions
|
|
$modHash->{DevAttrList}; # Attributes to add or overwrite devInfo definitions
|
|
}
|
|
|
|
|
|
1;
|
|
|
|
=pod
|
|
=begin html
|
|
|
|
<a name="ModbusAttr"></a>
|
|
<h3>ModbusAttr</h3>
|
|
<ul>
|
|
ModbusAttr uses the low level Modbus module 98_Modbus.pm to provide a generic Modbus module for devices that can be defined by attributes similar to the way HTTPMOD works for devices with a web interface.
|
|
<br><br>
|
|
<b>Prerequisites</b>
|
|
<ul>
|
|
<li>
|
|
This module requires the basic Modbus module which itsef DevIO which again requires Device::SerialPort or Win32::SerialPort module.
|
|
</li>
|
|
</ul>
|
|
<br>
|
|
|
|
<a name="ModbusAttrDefine"></a>
|
|
<b>Define</b>
|
|
<ul>
|
|
<code>define <name> ModbusAttr <Id> <Interval></code><br>
|
|
or<br>
|
|
<code>define <name> ModbusAttr <Id> <Interval> <Address:Port> <RTU|TCP></code><br>
|
|
<br>
|
|
The module connects to the Modbus device with Modbus Id <Id> through an already defined modbus device
|
|
or directly through Modbus TCP or Modbus RTU over TCP and actively requests data from that device every <Interval> seconds <br>
|
|
<br>
|
|
Examples:<br>
|
|
<br>
|
|
<ul><code>define WP ModbusAttr 1 60</code></ul><br>
|
|
to go through a serial interface managed by an already defined basic modbus device.<br>
|
|
or <br>
|
|
<ul><code>define WP ModbusAttr 5 60 192.168.1.122:504 TCP</code></ul><br>
|
|
to talk Modbus TCP <br>
|
|
or <br>
|
|
<ul><code>define WP ModbusAttr 3 60 192.168.1.122:8000 RTU</code></ul><br>
|
|
to talk Modbus RTU over TCP<br>
|
|
</ul>
|
|
<br>
|
|
|
|
<a name="ModbusAttrConfiguration"></a>
|
|
<b>Configuration of the module</b><br><br>
|
|
<ul>
|
|
The data objects (holding registers, input registers, coils or discrete inputs) of the device to be queried are defined using attributes.
|
|
The attributes assign objects with their address to readings inside fhem and control
|
|
how these readings are calculated from the raw values and how they are formatted.<br>
|
|
Objects can also be written to the device and attributes define how this is done.<br><br>
|
|
|
|
Example:<br>
|
|
<pre>
|
|
define PWP ModbusAttr 5 30
|
|
attr PWP obj-h256-reading Temp_Wasser_ein
|
|
attr PWP obj-h256-expr $val/10
|
|
|
|
attr PWP obj-h258-reading Temp_Wasser_Aus
|
|
attr PWP obj-h258-expr $val/10
|
|
|
|
attr PWP obj-h262-reading Temp_Luft
|
|
attr PWP obj-h262-expr $val / 10
|
|
|
|
attr PWP obj-h770-reading Temp_Soll
|
|
attr PWP obj-h770-expr $val / 10
|
|
attr PWP obj-h770-set 1
|
|
attr PWP obj-h770-setexpr $val * 10
|
|
attr PWP obj-h770-max 32
|
|
attr PWP obj-h770-min 10
|
|
attr PWP obj-h770-hint 8,10,20,25,28,29,30,30.5,31,31.5,32
|
|
|
|
attr PWP dev-h-combine 5
|
|
attr PWP dev-h-defPoll 1
|
|
|
|
attr PWP room Pool-WP
|
|
attr PWP stateFormat {sprintf("%.1f Grad", ReadingsVal($name,"Temp_Wasser_Ein",0))}
|
|
attr PWP webCmd Temp_Soll
|
|
</pre>
|
|
|
|
Attributes to define data objects start with obj- followed by a code that identifies the type and address
|
|
of the data object. <br>
|
|
Modbus devices offer the following types of data objects: holding registers (16 bit objects that can be read and written),
|
|
input registers (16 bit objects that can only be read), coils (single bit objects that can be read and written)
|
|
or discrete inputs (single bit objects that can only be read).
|
|
<br>
|
|
The module uses the first character of these data object types to define attributes.
|
|
Thus h770 refers to a holding register with the decimal address 770 and c120 refers to a coil with address 120.
|
|
The address has to be specified as pure decimal number without any leading zeros or spaces.<br><br>
|
|
|
|
<code>attr PWP obj-h258-reading Temp_Wasser_Aus</code> defines a reading with the name Temp_Wasser_Aus that is read from the Modbus holding register at address 258.<br>
|
|
With the attribute ending on <code>-expr</code> you can define a perl expression to do some conversion or calculation on the raw value read from the device.
|
|
In the above example the raw value has to be devided by 10 to get the real value.<br><br>
|
|
|
|
An object attribute ending on <code>-set</code> creates a fhem set option.
|
|
In the above example the reading Temp_Soll can be changed to 12 degrees by the user with the fhem command <code>set PWP Temp_Soll 12</code><br>
|
|
The object attributes ending on <code>-min</code> and <code>-max</code> define min and max values for input validation
|
|
and the attribute ending on <code>-hint</code> will tell fhem to create a selection list so the user can graphically select the defined values.<br><br>
|
|
|
|
To define general properties of the device you can specify attributes starting with <code>dev-</code>.
|
|
E.g. with <code>dev-timing-timeout</code> you can specify the timeout when waiting for a response from the device.
|
|
With <code>dev-h-</code> you can specify several default values or general settings for all holding registers
|
|
like the function code to be used when reading or writing holding registers.
|
|
These attributes are optional and the module will use defaults that work in most cases. <br>
|
|
<code>dev-h-combine 5</code> for example allows the module to combine read requests to objects having an address that differs 5 or less into one read request.
|
|
Without setting this attribute the module will start individual read requests for each object.
|
|
Typically the documentation for the modbus interface of a given device states the maximum number of objects that can be read in one function code 3 request.
|
|
</ul>
|
|
|
|
<a name="ModbusAttrSet"></a>
|
|
<b>Set-Commands</b><br>
|
|
<ul>
|
|
are created based on the attributes defining the data objects.<br>
|
|
Every object for which an attribute like <code>obj-xy-set</code> is set to 1 will create a valid set option.
|
|
</ul>
|
|
<br>
|
|
<a name="ModbusAttrGet"></a>
|
|
<b>Get-Commands</b><br>
|
|
<ul>
|
|
All readings are also available as Get commands. Internally a Get command triggers the corresponding
|
|
request to the device and then interprets the data and returns the right field value.
|
|
To avoid huge option lists in FHEMWEB, the objects visible as Get in FHEMWEB can be defined by setting an attribute <code>obj-xy-showget</code> to 1.
|
|
</ul>
|
|
<br>
|
|
<a name="ModbusAttrattr"></a>
|
|
<b>Attributes</b><br><br>
|
|
<ul>
|
|
<li><a href="#do_not_notify">do_not_notify</a></li>
|
|
<li><a href="#readingFnAttributes">readingFnAttributes</a></li>
|
|
<br>
|
|
<li><b>alignTime</b></li>
|
|
Aligns each periodic read request for the defined interval to this base time. This is typcally something like 00:00 (see the Fhem at command)
|
|
<li><b>enableControlSet</b></li>
|
|
enables the built in set commands interval, stop, start and reread
|
|
|
|
<br>
|
|
please also notice the attributes for the physical modbus interface as documented in 98_Modbus.pm
|
|
<br>
|
|
|
|
the following list of attributes can be applied to any data object by specifying the objects type and address in the variable part.
|
|
For many attributes you can also specify default values per object type (see dev- attributes later) or you can specify an object attribute without type and address
|
|
(e.g. obj-len) which then applies as default for all objects:
|
|
<li><b>obj-[cdih][1-9][0-9]*-reading</b></li>
|
|
define the name of a reading that corresponds to the modbus data object of type c,d,i or h and a decimal address (e.g. obj-h225-reading).
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-name</b></li>
|
|
defines an optional internal name of this data object (this has no meaning for fhem and serves mainly documentation purposes.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-set</b></li>
|
|
if set to 1 then this data object can be changed (works only for holding registers and coils since discrete inputs and input registers can not be modified by definition.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-min</b></li>
|
|
defines a lower limit to the value that can be written to this data object. This ist just used for input validation.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-max</b></li>
|
|
defines an upper limit to the value that can be written to this data object. This ist just used for input validation.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-hint</b></li>
|
|
this is used for set options and tells fhemweb what selection to display for the set option (list or slider etc.)
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-expr</b></li>
|
|
defines a perl expression that converts the raw value read from the device.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-map</b></li>
|
|
defines a map to convert values read from the device to more convenient values when the raw value is read from the device
|
|
or back when the value to write has to be converted from the user value to a raw value that can be written.
|
|
Example: 0:mittig, 1:oberhalb, 2:unterhalb
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-setexpr</b></li>
|
|
defines a perl expression that converts the user specified value in a set to a raw value that can be sent to the device.
|
|
This is typically the inversion of -expr above.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-format</b></li>
|
|
defines a format string to format the value read e.g. %.1f
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-len</b></li>
|
|
defines the length of the data object in registers. It defaults to 1.
|
|
Some devices store 32 bit floating point values in two registers. In this case you should set this attribute to two.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-unpack</b></li>
|
|
defines the unpack code to convert the raw data string read from the device to a reading.
|
|
For an unsigned integer in big endian format this would be "n",
|
|
for a signed 16 bit integer in big endian format this would be "s>"
|
|
and for a 32 bit big endian float value this would be "f>". (see the perl documentation of the pack function).<br>
|
|
Please note that you also have to set a -len attribute (for this object or for the device) if you specify an unpack code that consumes data from more than one register.<br>
|
|
For a 32 bit float len should be at least 2.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-revRegs</b></li>
|
|
this is only applicable to objects that span several input registers or holding registers. <br>
|
|
when they are read then the order of the registers will be reversed before
|
|
further interpretation / unpacking of the raw register string
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-bswapRegs</b></li>
|
|
this is applicable to objects that span several input or holding registers. <br>
|
|
after the registers have been read, all 16-bit values are treated big-endian and are reversed to little-endian by swapping the two 8 bit bytes.
|
|
This functionality is most likely used for reading (ASCII) strings from the device that are stored as big-endian 16-bit values. <br>
|
|
example: original reading is "324d3130203a57577361657320722020". After applying bswapRegs, the value will be "4d3230313a2057576173736572202020"
|
|
which will result in the ASCII string "M201: WWasser ". Should be used with "(a*)" as -unpack value.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-decode</b></li>
|
|
defines an encoding to be used in a call to the perl function decode to convert the raw data string read from the device to a reading.
|
|
This can be used if the device delivers strings in an encoding like cp850 instead of utf8.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-encode</b></li>
|
|
defines an encoding to be used in a call to the perl function encode to convert the raw data string read from the device to a reading.
|
|
This can be used if the device delivers strings in an encoding like cp850 and after decoding it you want to reencode it to e.g. utf8.
|
|
<br>
|
|
|
|
<li><b>obj-[cdih][1-9][0-9]*-showget</b></li>
|
|
every reading can also be requested by a get command. However these get commands are not automatically offered in fhemweb.
|
|
By specifying this attribute, the get will be visible in fhemweb.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-poll</b></li>
|
|
if set to 1 then this obeject is included in the cyclic update request as specified in the define command.
|
|
If not set, then the object can manually be requested with a get command, but it is not automatically updated each interval.
|
|
Note that this setting can also be specified as default for all objects with the dev- atributes described later.
|
|
<br>
|
|
<li><b>obj-[cdih][1-9][0-9]*-polldelay</b></li>
|
|
this attribute allows to poll objects at a lower rate than the interval specified in the define command.
|
|
You can either specify a time in seconds or number prefixed by "x" which means a multiple of the interval of the define command.<br>
|
|
If you specify a normal numer then it is interpreted as minimal time between the last read and another automatic read.
|
|
Please note that this does not create an additional interval timer.
|
|
Instead the normal interval timer defined by the interval of the define command will check if this reading is due or not yet.
|
|
So the effective interval will always be a multiple of the interval of the define.
|
|
<br>
|
|
<br>
|
|
<li><b>dev-([cdih]-)*read</b></li>
|
|
specifies the function code to use for reading this type of object.
|
|
The default is 3 for holding registers, 1 for coils, 2 for discrete inputs and 4 for input registers.
|
|
<br>
|
|
<li><b>dev-([cdih]-)*write</b></li>
|
|
specifies the function code to use for writing this type of object.
|
|
The default is 6 for holding registers and 5 for coils. Discrete inputs and input registers can not be written by definition.
|
|
<br>
|
|
<li><b>dev-([cdih]-)*combine</b></li>
|
|
defines how many adjacent objects can be read in one request. If not specified, the default is 1
|
|
<br>
|
|
<li><b>dev-([cdih]-)*defLen</b></li>
|
|
defines the default length for this object type. If not specified, the default is 1
|
|
<br>
|
|
<li><b>dev-([cdih]-)*defFormat</b></li>
|
|
defines a default format string to use for this object type in a sprintf function on the values read from the device.
|
|
<br>
|
|
<li><b>dev-([cdih]-)*defExpr</b></li>
|
|
defines a default Perl expression to use for this object type to convert raw values read.
|
|
<br>
|
|
<li><b>dev-([cdih]-)*defUnpack</b></li>
|
|
defines the default unpack code for this object type.
|
|
<br>
|
|
<li><b>dev-([cdih]-)*defRevRegs</b></li>
|
|
defines that the order of registers for objects that span several registers will be reversed before
|
|
further interpretation / unpacking of the raw register string
|
|
<br>
|
|
<li><b>dev-([cdih]-)*defBswapRegs</b></li>
|
|
per device default for swapping the bytes in Registers (see obj-bswapRegs above)
|
|
<br>
|
|
<li><b>dev-([cdih]-)*defDecode</b></li>
|
|
defines a default for decoding the strings read from a different character set e.g. cp850
|
|
<br>
|
|
<li><b>dev-([cdih]-)*defEncode</b></li>
|
|
defines a default for encoding the strings read (or after decoding from a different character set) e.g. utf8
|
|
<br>
|
|
|
|
<li><b>dev-([cdih]-)*defPoll</b></li>
|
|
if set to 1 then all objects of this type will be included in the cyclic update by default.
|
|
<br>
|
|
<li><b>dev-([cdih]-)*defShowGet</b></li>
|
|
if set to 1 then all objects of this type will have a visible get by default.
|
|
<br>
|
|
<li><b>dev-timing-timeout</b></li>
|
|
timeout for the device (defaults to 2 seconds)
|
|
<br>
|
|
<li><b>dev-timing-sendDelay</b></li>
|
|
delay to enforce between sending two requests to the device. Default ist 0.1 seconds.
|
|
<br>
|
|
<li><b>dev-timing-commDelay</b></li>
|
|
delay between the last read and a next request. Default ist 0.1 seconds.
|
|
<br>
|
|
<li><b>nextOpenDelay</b></li>
|
|
delay for Modbus-TCP connections. This defines how long the module should wait after a failed TCP connection attempt before the next reconnection attempt. This defaults to 60 seconds.
|
|
|
|
<li><b>maxTimeoutsToReconnect</b></li>
|
|
this attribute is only valid for TCP connected devices. In such cases a disconnected device might stay undetected and lead to timeouts until the TCP connection is reopened. This attribute specifies after how many timeouts an automatic reconnect is tried.
|
|
<li><b>disable</b></li>
|
|
stop communication with the device while this attribute is set to 1
|
|
<br>
|
|
</ul>
|
|
<br>
|
|
</ul>
|
|
|
|
=end html
|
|
=cut
|