*** HMCCU/HMCCUDEV - Modules for FHEM - Homematic CCU integration ***
=======================================================================
* Document covers HMCCU/HMCCUDEV/HMCCUCHN version 2.1 (RPC server)
* Please read carefully before using the modules.
* Last modified: 25.11.2015
----------------------------------------------
Content
----------------------------------------------
1 HMCCU Introduction
1.1 HMCCU Description
1.2 HMCCU Requirements & Installation
2 HMCCU Usage
2.1 HMCCU Set Commands
2.2 HMCCU Get Commands
2.3 HMCCU Attributes
2.4 HMCCU Parameter File
2.5 RPC daemon
3 HMCCUDEV Introduction
3.1 HMCCUDEV Description
3.2 HMCCUDEV Requirements
4 HMCCUDEV Usage
4.1 HMCCUDEV Set Commands
4.2 HMCCUDEV Get Commands
4.3 HMCCUDEV Attributes
5 HMCCUCHN Usage
5.1 HMCCUCHN Set Commands
5.2 HMCCUCHN Get Commands
5.3 HMCCUCHN Attributes
6 Hints and Tips
6.1 Requesting information from CCU
6.2 Executing FHEM commands on CCU
6.3 Use RAM disk for /tmp on Raspbian
----------------------------------------------
====================================
1 HMCCU Introduction
====================================
------------------------------------
1.1 HMCCU Description
------------------------------------
The modules HMCCU, HMCCUDEV and HMCCUCHN provide a simple interface between FHEM
and a Homematic CCU2. HMCCU is the IO device for the communication with the CCU.
The states and values of CCU channels and variables are not updated automatically
in FHEM. You have to define AT devices with get commands to ensure a continuous
update of CCU readings in FHEM or use the external RPC server.
--------------------------------------
1.2 HMCCU Requirements & Installation
--------------------------------------
The module HMCCU no longer requires the XML-API CCU addon. The FHEM module requires
the packages LWP::UserAgent, Time::HiRes, RPC::XML::Client and RPCQueue.
The RPC server ccurpcd.pl requires the packages RPC::XML::Server, RPC::XML::Client,
RPCQueue and IO::Socket::INET.
All module files 88_HMCCU*, RPCQueue.pm and the RPC daemon ccurpcd.pl must be copied
into the folder FHEM under the FHEM installation directory.
NOTE: RPCQueue.pm is a bug fixed copy of File::Queue and part of the HMCCU installation
package. It's not available via CPAN!
====================================
2 HMCCU Usage
====================================
Define a new IO device for communication with Homematic CCU:
define <name> HMCCU <hostname_or_IP>
The only parameter is the name or the IP address of the Homematic CCU. All
other adjustments are done by setting attributes.
Some commands use device, channel or datapoint addresses. A channel address has
the following format:
[<interface>.]<device-address>:<channel-number>
A device address is a channel address without the channel number. The default
value for <interface> is "BidCoS-RF". A datapoint is identified by
<channel-address>.<datapoint-name>
or
<channel-name>.<datapoint-name>
A <channel-name> or a <device-name> is the alias for an device or channel defined
in the CCU.
IMPORTANT NOTE: During device definition HMCCU reads the available CCU devices.
This request must be repeated by using command "get devicelist" after a reload
of the module or after modification or definition of devices in the CCU. Otherwise
HMCCU, HMCCUDEV and HMCCUCHN won't work correctly. It's recommended to define
an automatic device synchronization (i.e. daily) with AT and command
'get <name> devicelist'.
------------------------------------
2.1 HMCCU Set commands
------------------------------------
If attribute 'stateval' is set the specified string substitutions are applied
for values before setting the device state, a variable or a datapoint value.
This is important because CCU states are often 'true' or 'false' while in FHEM
one like to use 'on' or 'off'. So i.e. setting 'stateval' to 'on:true,off:false'
will ensure that FHEM commands 'on' and 'off' are replaced by 'true' and 'false'
before transmitting them to the CCU.
Set state of a CCU channel:
set <name> devstate {<channel-name>|<channel-address>} <value> [...]
Parameters <channel-name> or <channel-address> refer to the CCU device
channel with datapoint STATE. This default datapoint can be changed by setting
attribute 'statedatapoint'.
If more than one <value> is specified the values are concatinated by blanks
to one text string.
Set value of a CCU device datapoint:
set <name> datapoint {<channel-name>|<channel-address>}.<datapoint> <value> [...]
Parameters correspond to 'devstate' command. In addition the name of a CCU
channel datapoint must be specified.
Set value of a CCU system variable:
set <name> var <variable> <value> [...]
The variable must exist in CCU. It's not created automatically.
Execute CCU program:
set <name> execute <program>
The program is executed even if it's deactivated in CCU.
Execute Homematic script:
set <name> hmscript <script-file>
If script returns parameter=value pairs via standard output these values are
stored as readings.
------------------------------------
2.2 HMCCU Get commands
------------------------------------
If attribute 'ccureadings' is set to 1 (default) the results of the get commands
are stored in readings. By default the reading names correspond to the CCU
datapoints, including the channel-name. This behaviour can be changed by setting
the attribute 'ccureadingformat'. If attribute 'ccureadings' is set to 0 the
results of the get commands are displayed in the browser window. No readings will
be set in this case. Some get commands allow an optional parameter <reading>. If
this parameter is specified the CCU value is stored in FHEM using this reading name.
The attribute 'updatemode' controls wether readings are updated in the IO device,
in client devices only or both in IO device and client devices.
With attribute 'substitute' one can define expressions which are substituted by
strings before CCU values are stored in readings. For example if CCU reports
device states as "true" or "false" these values can be replaced by "open" or
"closed" by setting "substitute" to "true:open,false:closed". The attribute
'substitute' is ignored if the same attribute is defined in a client device.
Get values of channel datapoints (supports multiple channels):
get <name> channel {<channel-name>|<channel-address>}[.<datapoint_exp>] [...]
Attention: There's no blank between channel and datapoint. If datapoint is
not specified all datapoints will be read. The command accepts a regular
expression as parameter <datapoint_exp>.
Get value of datapoint:
get <name> datapoint {<channel-name>|<channel-address>}.<datapoint> [<reading>]
Read list of devices and channels from CCU:
get <name> devicelist [dump]
This command must be executed after HMCCU is reloaded or after devices are
defined, modified or deleted in the CCU. Otherwise HMCCU does not know
the alias names of CCU devices and most of the get/set commands will fail.
With option 'dump' all devices/channels are displayed in browser window.
Get state of channel:
get <name> devstate {<channel-name>|<channel-address>} [<reading>]
Specified channel must contain the datapoint 'STATE'. This default datapoint
can be modified by setting attribute 'statedatapoint'.
Get multiple channels and datapoints:
get <name> parfile [<parfile>]
If attribute 'parfile' is set parameter <parfile> can be omitted. See
parameter file description below.
Get CCU variable values:
get <name> vars <varname_exp>
Variable name can be a regular expression. Variables are stored as readings
with same name as in CCU.
------------------------------------
2.3 HMCCU Attributes
------------------------------------
Set reading name format (default is 'name'):
attr <name> ccureadingformat { name | address }
Control reading update in IO and client devices (default is 'hmccu'):
attr <name> updatemode { hmccu | both | client }
Control reading creation (default is 1):
attr <name> ccureadings { 0 | 1 }
Set datapoint for "get/set devstate" commands (default is 'STATE'):
attr <name> statedatapoint <datapoint>
Remove character from CCU device or variable specification in set commands:
attr <name> stripchar <character>
If a variable name ends with the specified character this character will be
removed.
Specify name of parameter file for command "get parfile":
attr <name> parfile <parfile>
Set interval for RPC event processing:
attr <name> rpcinterval { 3 | 5 | 10 }
Set interval in seconds for reading RPC events from RPC event queue.
Set port of CCU RPC interface (default is 2001):
attr <name> rpcport <port>
Set RPC event queue file (default is /tmp/ccuqueue):
attr <name> rpcqueue <filename>
Parameter <filename> is a prefix. The RPC event queue consists of two files
with extension .idx and .dat.
Start/stop RPC server:
attr <name> rpcserver { on | off }
After starting the RPC server it takes 3 minutes until events from CCU arrive.
Stopping RPC server can take a few seconds.
Specify text substitutions for values in set commands:
attr <name> stateval <text1>:<subtext1>[,...]
Note: Parameters <textn> are no regular expressions.
Specify text substitutions for values returned by get commands:
attr <name> substitute <regexp1>:<text1>[,...]
------------------------------------
2.4 HMCCU Parameter files
------------------------------------
A parameter file contains a list of CCU channel or datapoint definitions. Each
line can contain a text substitution rule. A parameter file is used by command
"get parfile". The format of a parfile entry is:
{<channel-name>|<channel-address>}[.<datapoint_exp>] [<regexp1>:<subtext1>[,...]]
First part corresponds to command 'get channel'. Empty lines and lines starting
with a '#' are ignored.
------------------------------------
2.5 RPC daemon
------------------------------------
Because of several restrictions of FHEM regarding socket communication and
forking external processes the RPC daemon is realized as a standalone process.
The communication between ccurpcd and FHEM happens by using a file based FIFO
queue. On systems running on SD cards like Raspberry PI it's recommended to
set the attribute 'rpcqueue' pointing to a file located on a RAM disk (see
section 6.3 for more information about setting up a RAM disk on Raspbian).
ccurpcd is started under user 'fhem'. So this user must have the permission to
read and write data on from/into queue file and also write log file entries in
the standard FHEM log directory. The daemon writes error messages to file
ccurpcd.log in the FHEM log directory.
The RPC daemon is controlled via attribute 'rpcserver'. After setting this
attribute to "on" the HMCCU module will start ccurpcd as a separate process.
The PID of ccurpcd is stored in the internal "RPCPID". After start of ccurpcd
it takes 3 minnutes until first events from CCU arrive in FHEM (don't know
why - ask EQ-3 ;-)
The RPC daemon is stopped when setting 'rpcserver' to "off" or by sending a
signal "INT" to the process. Because ccurpcd will gracefully shutdown the
CCU interface it can take some time until process disappears. After process
has been terminated the internal "RPCPID" is deleted.
For more information see attributes 'rpcport', 'rpcserver', 'rpcqueue' and
'rpcinterval'.
====================================
3 HMCCUDEV Introduction
====================================
------------------------------------
3.1 HMCCUDEV Description
------------------------------------
HMCCUDEV is used to define HMCCU client devices for CCU devices. Note: HMCCU
can be used standalone without defining client devices.
------------------------------------
3.2 HMCCUDEV Requirements
------------------------------------
See 1.2 HMCCU Requirements. The module 88_HMCCUDEV.pm must be copied into folder
FHEM under the FHEM installation directory. A IO device of type HMCCU must be
defined before defining any client devices.
====================================
4 HMCCUDEV Usage
====================================
Define a new client device:
define <name> HMCCUDEV {<Device-Name>|<Device-Address>} [<channel-number>] [readonly]
Parameter <Device-Address> is the CCU device address without the channel number.
The CCU device must be known by HMCCU. If the device can't be found the device
list of the HMCCU device must be updated with command 'get devicelist'.
The channel number for devstate commands can be specified with parameter
<channel-number> or via attribute 'statechannel'.
The keyword 'readonly' declares a device as read only (i.e. a sensor). For read
only devices no set command is available.
------------------------------------
4.1 HMCCUDEV Set Commands
------------------------------------
Set value of datapoint:
set <name> datapoint <channel-number>.<datapoint-name> <value> [...]
Set state of device:
set <name> devstate <value>
set <name> <state-value>
If attribute 'statevals' is defined 'devstate' can be ommitted. The channel
number which contains datapoint 'STATE' must be set via attribute 'statechannel'.
If no state channel is specified the command is not available. The default
datapoint 'STATE' can be modified by setting attribute 'statedatapoint'.
------------------------------------
4.2 HMCCUDEV Get Commands
------------------------------------
Get value of datapoint:
get <name> datapoint <channel-number>[.<datapoint-name>]
If no datapoibt is specified all datapoints for specified channel are read.
Get multiple datapoints of channel (supports multiple channels):
get <name> channel <channel-number>[.<datapoint-expr>] [...]
Parameter <datapoint-expr> is a regular expression. Default is .* (query all
datapoints of a channel).
Get state of device:
get <name> devstate
Requires the specification of the channel number which contains datapoint
"STATE" by using attribute 'statechannel'. The default datapoint "STATE"
can be modified by setting attribute 'statedatapoint'.
------------------------------------
4.3 HMCCUDEV Attributes
------------------------------------
Client device attributes overwrite corresponding HMCCU attributes!
Set reading name format (default is 'name'):
attr <name> ccureadingformat { name | address | datapoint }
If set to 'datapoint' the reading name is the datapoint name without channel.
Control reading creation (default is 1):
attr <name> ccureadings { 0 | 1 }
Set datapoint for 'devstate' command (default is "STATE"):
attr <name> statedatapoint <datapoint>
Specify IO device for client device:
attr <name> IODev <HMCCU-Device>
Normally this is set automatically during HMCCUDEV device definition.
Specify channel number of STATE datapoint:
attr <name> statechannel <channel-number>
If no statechannel is set the commands 'get/set devstate' are not available.
Specify text substitutions for values in set commands:
attr <name> stateval <text1>:<subtext1>[,...]
The values <textn> are available as set commands, i.e.
attr switch1 stateval on:true,off:false
set switch1 on
set switch1 off
set switch1 devstate on
Specify text substitutions for values returned by get commands:
attr <name> substitute <regexp1>:<text1>[,...]
====================================
5 HMCCUCHN Usage
====================================
Define a new client device:
define <name> HMCCUCHN {<Channel-Name>|<Channel-Address>} [readonly]
Parameter <Channel-Address> is the CCU channel address including the channel
number. If <Channel-Name> is specified it must be known by HMCCU. If the channel
can't be found the device list of the HMCCU device must be updated with command
'get devicelist'. The keyword 'readonly' declares a channel as read only (i.e.
a sensor). For read only channels no set command is available.
------------------------------------
5.1 HMCCUCHN Set Commands
------------------------------------
Set value of datapoint:
set <name> datapoint <datapoint-name> <value> [...]
Set state of channel:
set <name> devstate <value>
set <name> <state-value>
If attribute 'statevals' is defined 'devstate' can be ommitted. The default
datapoint "STATE" can be modified by setting attribute 'statedatapoint'.
------------------------------------
4.2 HMCCUCHN Get Commands
------------------------------------
Get value of datapoint:
get <name> datapoint [<datapoint-name>]
If no datapoint is specified all datapoints are read.
Get multiple datapoints:
get <name> channel [<datapoint-exp>]
Parameter <datapoint-expr> is a regular expression. Default is .* (query all
datapoints of a channel).
Get state of device:
get <name> devstate
The default datapoint "STATE" can be modified by setting attribute
'statedatapoint'.
------------------------------------
4.3 HMCCUCHN Attributes
------------------------------------
Client device attributes overwrite corresponding HMCCU attributes!
Set reading name format (default is 'name'):
attr <name> ccureadingformat { name | address | datapoint }
If set to 'datapoint' the reading name is the datapoint name without channel.
Control reading creation (default is 1):
attr <name> ccureadings { 0 | 1 }
Set datapoint for "devstate" command (default is "STATE"):
attr <name> statedatapoint <datapoint>
Specify IO device for client device:
attr <name> IODev <HMCCU-Device>
Normally this is set automatically during HMCCUDEV device definition.
Specify text substitutions for values in set commands:
attr <name> stateval <text1>:<subtext1>[,...]
The values <textn> are available as set commands, i.e.
attr switch1 stateval on:true,off:false
set switch1 on
set switch1 off
set switch1 devstate on
Specify text substitutions for values returned by get commands:
attr <name> substitute <regexp1>:<text1>[,...]
====================================
6 Hints and tipps
====================================
------------------------------------
6.1 Requesting information from CCU
------------------------------------
By using XML-API one can query device names, channel names, channel addresses
and datapoint names from CCU. The following request queries device and channel
information:
http://ccuname-or-ip/config/xmlapi/devicelist.cgi?show_internal=1
The following request returns a list of datapoints with current values:
http://ccuname-or-ip/config/xmlapi/statelist.cgi?show_internal=1
------------------------------------
6.2 Executing FHEM commands on CCU
------------------------------------
It's possible to execute FHEM commands from CCU via the FHEM telnet port.
The following shell script encapsulates the necessary commands. It can
be placed somewhere under /etc/config/addons directory in CCU. The script
requires the installation of the netcat command (nc) on CCU (search for
the binary in google and install it somewhere in /etc/config/addons).
--- Start of script ---
#!/bin/sh
# Set name or IP address and port of FHEM server
FHEM_SERVER="myfhem"
FHEM_PORT=7072
# Set path to nc command
NCCMD="/etc/config/addons/scripts"
if [ $# -ne 1 ]; then
echo "Usage: $0 Command"
exit 1
fi
echo -e "$1\nquit\n" | $NCCMD/nc $FHEM_SERVER $FHEM_PORT
--- End of script ---
The script should be called from a CCU program by using the CUXD exec object
(requires installation of CUxD). If FHEM command contains blanks it should be
enclosed in double quotes.
--------------------------------------
6.3 Use RAM disk for /tmp on Raspbian
--------------------------------------
By default ccurpcd creates the queue files in directory /tmp. On systems which
are running on a SD card like Raspbian this can shorten the lifetime of the
SD card. To avoid this /tmp can be moved to a RAM disk:
1) Edit file /etc/fstab as user 'root' and append the following line
tmpfs /tmp tmpfs nodev,nosuid,relatime,size=100M 0 0
This will define /tmp as a RAM disk with a size of 100 MByte.
2) Restart the system.
*** Have fun! zap ***