<a name="OWX"></a>
<h3>OWX</h3>
<ul> FHEM module to commmunicate with 1-Wire bus devices <ul>
<li>via an active DS2480/DS2482/DS2490/DS9097U bus master interface attached to an
USB port or </li>
<li>via a passive DS9097 interface attached to an USB port or</li>
<li>via a network-attached CUNO</li>
</ul> Internally these interfaces are vastly different, read the corresponding <a
href="http://fhemwiki.de/wiki/Interfaces_f%C3%BCr_1-Wire"> Wiki pages </a>
<br />
<br />
<b>Example</b><br />
<ul>
<code>define OWio OWX /dev/ttyUSB1</code>
<br />
</ul>
<br />
<a name="OWXdefine">
<b>Define</b></a>
<ul>
<code>define &lt;name&gt; OWX &lt;serial-device&gt;</code> or <br />
<code>define &lt;name&gt; OWX &lt;cuno-device&gt;</code>
<br /><br /> Define a 1-Wire interface to communicate with a 1-Wire bus.<br />
<br />
<li>
<code>&lt;serial-device&gt;</code> The serial device (e.g. USB port) to which
the 1-Wire bus is attached.</li>
<li>
<code>&lt;cuno-device&gt;</code> The previously defined CUNO to which the 1-Wire
bus is attached. </li>
</ul>
<br />
<a name="OWXset">
<b>Set</b></a>
<ul>
<li><a name="owx_interval">
<code>set &lt;name&gt; interval &lt;value&gt;</code>
</a>
<br /><br /> sets the time period in seconds for "kicking" the 1-Wire bus
(default is 300 seconds). This means: <ul>
<li>With 1-Wire bus interfaces that do not supply power to the 1-Wire bus
(attr buspower parasitic), the 1-Wire bus is reset at these intervals. </li>
<li>With 1-Wire bus interfaces that supply power to the 1-Wire bus (attr
buspower = real), all temperature measurement devices on the bus receive
the command to start a temperature conversion (saves a lot of time when
reading) </li>
<li>With 1-Wire bus interfaces that contain a busmaster chip, the response
to a reset pulse contains information about alarms.</li>
</ul><br />
</li>
<li><a name="owx_followAlarms">
<code>set &lt;name&gt; followAlarms on|off</code>
</a>
<br /><br /> instructs the module to start an alarm search in case a reset pulse
discovers any 1-Wire device which has the alarm flag set. </li>
</ul>
<br />
<a name="OWXget">
<b>Get</b></a>
<ul>
<li><a name="owx_alarms"></a>
<code>get &lt;name&gt; alarms</code>
<br /><br /> performs an "alarm search" for devices on the 1-Wire bus and, if
found, generates an event in the log (not with CUNO). </li>
<br />
<li><a name="owx_devices"></a>
<code>get &lt;name&gt; devices</code>
<br /><br /> redicovers all devices on the 1-Wire bus. If a device found has a
previous definition, this is automatically used. If a device is found but has no
definition, it is autocreated. If a defined device is not on the 1-Wire bus, it
is autodeleted. </li>
<br />
<br />
</ul>
<a name="OWXattr">
<b>Attributes</b></a>
<ul>
<li><a name="OWXbuspower"><code>attr &lt;name&gt; buspower real|parasitic</code></a>
<br />tells FHEM whether power is supplied to the 1-Wire bus or not.</li>
<li>Standard attributes alias, comment, eventMap, logLevel, webCmd</li>
</ul>
</ul>
<!--+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++-->
<a name="OWAD"></a>
<h3>OWAD</h3>
<ul>FHEM module to commmunicate with 1-Wire A/D converters<br /><br /> Note:<br /> This
1-Wire module so far works only with the OWX interface module. Please define an <a
href="#OWX">OWX</a> device first. <br />
<br /><b>Example</b><br />
<ul>
<code>define OWX_AD OWAD 724610000000 45</code>
<br />
<code>attr OWX_AD DAlarm high</code>
<br />
<code>attr OWX_AD DFactor 31.907097</code>
<br />
<code>attr OWX_AD DHigh 50.0</code>
<br />
<code>attr OWX_AD DName RelHumidity|humidity</code>
<br />
<code>attr OWX_AD DOffset -0.8088</code>
<br />
<code>attr OWX_AD DUnit percent|%</code>
<br />
</ul><br />
<a name="OWADdefine"></a>
<b>Define</b>
<ul>
<code>define &lt;name&gt; OWAD [&lt;model&gt;] &lt;id&gt; [&lt;interval&gt;]</code>
<br /><br /> Define a 1-Wire A/D converter.<br /><br />
<li>
<code>[&lt;model&gt;]</code><br /> Defines the A/D converter model (and thus
1-Wire family id), currently the following values are permitted: <ul>
<li>model DS2450 with family id 20 (default if the model parameter is
omitted)</li>
</ul>
</li>
<li>
<code>&lt;id&gt;</code>
<br />12-character unique ROM id of the converter device without family id and
CRC code </li>
<li>
<code>&lt;interval&gt;</code>
<br />Measurement interval in seconds. The default is 300 seconds. </li>
<br />
</ul>
<br />
<a name="OWADset">
<b>Set</b></a>
<ul>
<li><a name="owad_interval">
<code>set &lt;name&gt; interval &lt;int&gt;</code></a><br /> Measurement
interval in seconds. The default is 300 seconds. </li>
</ul>
<br />
<a name="OWADget">
<b>Get</b></a>
<ul>
<li><a name="owad_id">
<code>get &lt;name&gt; id</code></a>
<br /> Returns the full 1-Wire device id OW_FAMILY.ROM_ID.CRC </li>
<li><a name="owad_present">
<code>get &lt;name&gt; present</code>
</a>
<br /> Returns 1 if this 1-Wire device is present, otherwise 0. </li>
<li><a name="owad_interval2">
<code>get &lt;name&gt; interval</code></a><br />Returns measurement interval
in seconds. </li>
<li><a name="owad_reading">
<code>get &lt;name&gt; reading</code></a><br />Obtain the measuement values. </li>
<li><a name="owad_alarm">
<code>get &lt;name&gt; alarm</code></a><br />Obtain the alarm values. </li>
<li><a name="owad_status">
<code>get &lt;name&gt; status</code></a><br />Obtain the i/o status values.
</li>
</ul>
<br />
<a name="OWADattr">
<b>Attributes</b></a>
<ul>
<li><a name="owad_stateAL0"><code>attr &lt;name&gt; stateAL0
&lt;string&gt;</code></a>
<br />character string for denoting low normal condition, default is green down
triangle, e.g. the code &lt;span
style="color:green"&gt;&amp;#x25BE;&lt;/span&gt; leading to the sign <span
style="color:green">&#x25BE;</span>
</li>
<li><a name="owad_stateAH0"><code>attr &lt;name&gt; stateAH0
&lt;string&gt;</code></a>
<br />character string for denoting high alarm condition, default is green
upward triangle, e.g. the code &lt;span
style="color:green"&gt;&amp;#x25B4;&lt;/span&gt; leading to the sign <span
style="color:green">&#x25B4;</span>
</li>
<li><a name="owad_stateAL1"><code>attr &lt;name&gt; stateAL1
&lt;string&gt;</code></a>
<br />character string for denoting low alarm condition, default is red down
triangle, e.g. the code &lt;span style="color:red"&gt;&amp;#x25BE;&lt;/span&gt;
leading to the sign <span style="color:red">&#x25BE;</span></li>
<li><a name="owad_stateAH1"><code>attr &lt;name&gt; stateAH1
&lt;string&gt;</code></a>
<br />character string for denoting high alarm condition, default is red upward
triangle, e.g. the code &lt;span style="color:red"&gt;&amp;#x25B4;&lt;/span&gt;
leading to the sign <span style="color:red">&#x25B4;</span>
</li>
</ul> For each of the following attributes, the channel identification A,B,C,D may be
used. <ul>
<li><a name="owad_cname"><code>attr &lt;name&gt; &lt;channel&gt;Name
&lt;string&gt;|&lt;string&gt;</code></a>
<br />name for the channel | a type description for the measured value. </li>
<li><a name="owad_cunit"><code>attr &lt;name&gt; &lt;channel&gt;Unit
&lt;string&gt;|&lt;string&gt;</code></a>
<br />unit of measurement for this channel | its abbreviation. </li>
<li><a name="owad_coffset"><code>attr &lt;name&gt; &lt;channel&gt;Offset
&lt;float&gt;</code></a>
<br />offset added to the reading in this channel. </li>
<li><a name="owad_cfactor"><code>attr &lt;name&gt; &lt;channel&gt;Factor
&lt;float&gt;</code></a>
<br />factor multiplied to (reading+offset) in this channel. </li>
<li><a name="owad_calarm"><code>attr &lt;name&gt; &lt;channel&gt;Alarm
&lt;string&gt;</code></a>
<br />alarm setting in this channel, either both, low, high or none (default). </li>
<li><a name="owad_clow"><code>attr &lt;name&gt; &lt;channel&gt;Low
&lt;float&gt;</code></a>
<br />measurement value (on the scale determined by offset and factor) for low
alarm. </li>
<li><a name="owad_chigh"><code>attr &lt;name&gt; &lt;channel&gt;High
&lt;float&gt;</code></a>
<br />measurement value (on the scale determined by offset and factor) for high
alarm. </li>
<li>Standard attributes alias, comment, eventMap, logLevel, webCmd</li>
</ul>
</ul>
<!--+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++-->
<a name="OWCOUNT"></a>
<h3>OWCOUNT</h3>
<ul>FHEM module to commmunicate with 1-Wire Counter/RAM DS2423 #<br /><br /> Note:<br />
This 1-Wire module so far works only with the OWX interface module. Please define an <a
href="#OWX">OWX</a> device first. <br />
<br /><b>Example</b><br />
<ul>
<code>define OWX_C OWCOUNT DS2423 CE780F000000 300</code>
<br />
<code>attr OWX_C AName Water|volume</code>
<br />
<code>attr OWX_C AUnit liters|l</code>
<br />
<code>attr OWX_CAMode daily</code>
<br />
</ul><br />
<a name="OWCOUNTdefine"></a>
<b>Define</b>
<ul>
<code>define &lt;name&gt; OWCOUNT [&lt;model&gt;] &lt;id&gt;
[&lt;interval&gt;]</code>
<br /><br /> Define a 1-Wire counter.<br /><br />
<li>
<code>[&lt;model&gt;]</code><br /> Defines the counter model (and thus 1-Wire
family id), currently the following values are permitted: <ul>
<li>model DS2423 with family id 1D (default if the model parameter is
omitted)</li>
</ul>
</li>
<li>
<code>&lt;id&gt;</code>
<br />12-character unique ROM id of the converter device without family id and
CRC code </li>
<li>
<code>&lt;interval&gt;</code>
<br />Measurement interval in seconds. The default is 300 seconds. </li>
</ul>
<br />
<a name="OWCOUNTset">
<b>Set</b></a>
<ul>
<li><a name="owcount_interval">
<code>set &lt;name&gt; interval &lt;int&gt;</code></a><br /> Measurement
interval in seconds. The default is 300 seconds. </li>
<li><a name="owcount_memory">
<code>set &lt;name&gt; memory &lt;page&gt;</code></a><br />Write 32 bytes to
memory page 0..13 </li>
<li><a name="owcount_midnight">
<code>set &lt;name&gt; midnight &lt;channel-name&gt;</code></a><br />Write
the day's starting value for counter &lt;channel&gt; (A, B or named channel, see
below)</li>
</ul>
<br />
<a name="OWCOUNTget">
<b>Get</b></a>
<ul>
<li><a name="owcount_id">
<code>get &lt;name&gt; id</code></a>
<br /> Returns the full 1-Wire device id OW_FAMILY.ROM_ID.CRC </li>
<li><a name="owcount_present">
<code>get &lt;name&gt; present</code>
</a>
<br /> Returns 1 if this 1-Wire device is present, otherwise 0. </li>
<li><a name="owcount_interval2">
<code>get &lt;name&gt; interval</code></a><br />Returns measurement interval
in seconds. </li>
<li><a name="owcount_memory2">
<code>get &lt;name&gt; memory &lt;page&gt;</code></a><br />Obtain 32 bytes
from memory page 0..13 </li>
<li><a name="owcount_midnight2">
<code>get &lt;name&gt; midnight &lt;channel-name&gt;</code></a><br />Obtain
the day's starting value for counter &lt;channel&gt; (A, B or named channel, see
below)</li>
<li><a name="owcount_counter">
<code>get &lt;name&gt; counter &lt;channel-name&gt;</code></a><br />Obtain
the current value for counter &lt;channel&gt; (A, B or named channel, see
below)</li>
<li><a name="owcount_counters">
<code>get &lt;name&gt; counters</code></a><br />Obtain the current value
both counters</li>
</ul>
<br />
<a name="OWCOUNTattr">
<b>Attributes</b></a>
<ul>For each of the following attributes, the channel identification A,B may be used.
<li><a name="owcount_cname"><code>attr &lt;name&gt; &lt;channel&gt;Name
&lt;string&gt;|&lt;string&gt;</code></a>
<br />name for the channel | a type description for the measured value. </li>
<li><a name="owcount_cunit"><code>attr &lt;name&gt; &lt;channel&gt;Unit
&lt;string&gt;|&lt;string&gt;</code></a>
<br />unit of measurement for this channel | its abbreviation. </li>
<li><a name="owcount_coffset"><code>attr &lt;name&gt; &lt;channel&gt;Offset
&lt;float&gt;</code></a>
<br />offset added to the reading in this channel. </li>
<li><a name="owcount_cfactor"><code>attr &lt;name&gt; &lt;channel&gt;Factor
&lt;float&gt;</code></a>
<br />factor multiplied to (reading+offset) in this channel. </li>
<li><a name="owcount_cmode"><code>attr &lt;name&gt; &lt;channel&gt;Mode daily |
normal</code></a>
<br />factor multiplied to (reading+offset) in this channel. </li>
<li>Standard attributes alias, comment, eventMap, logLevel, webCmd</li>
</ul>
</ul>
<!--+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++-->
<a name="OWID"></a>
<h3>OWID</h3>
<ul>FHEM module for 1-Wire devices that know only their unique ROM ID<br />
<br />Note:<br /> This 1-Wire module so far works only with the OWX interface module.
Please define an <a href="#OWX">OWX</a> device first. <br />
<br /><b>Example</b><br />
<ul>
<code>define ROM1 OWX_ID OWCOUNT CE780F000000</code>
<br />
</ul><br />
<a name="OWIDdefine"></a>
<b>Define</b>
<ul>
<code>define &lt;name&gt; OWID &lt;id&gt; </code>
<br /><br /> Define a 1-Wire device.<br /><br />
<li>
<code>&lt;id&gt;</code>
<br />12-character unique ROM id of the converter device without family id and
CRC code </li>
</ul>
<br />
<a name="OWIDget">
<b>Get</b></a>
<ul>
<li><a name="owid_id">
<code>get &lt;name&gt; id</code></a>
<br /> Returns the full 1-Wire device id OW_FAMILY.ROM_ID.CRC </li>
<li><a name="owid_present">
<code>get &lt;name&gt; present</code>
</a>
<br /> Returns 1 if this 1-Wire device is present, otherwise 0. </li>
</ul>
<br />
</ul>
<!--+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++-->
<a name="OWLCD"></a>
<h3>OWLCD</h3>
<ul>FHEM module to commmunicate with the <a
href="http://www.louisswart.co.za/1-Wire_Overview.html">1-Wire LCD controller</a>
from Louis Swart (1-Wire family id FF). See also the corresponding <a
href="http://fhemwiki.de/wiki/1-Wire_Textdisplay">Wiki page.</a><br /><br />
Note:<br /> This 1-Wire module so far works only with the OWX interface module. Please
define an <a href="#OWX">OWX</a> device first. <br />
<br /><b>Example</b><br />
<ul>
<code>define OWX_LCD OWLCD 9F0700000100</code>
<br />
</ul>
<br />
<a name="OWLCDdefine"></a>
<b>Define</b>
<ul>
<code>define &lt;name&gt; OWLCD &lt;id&gt;</code>
<br /><br /> Define a 1-Wire LCD device.<br /><br />
<li>
<code>&lt;id&gt;</code>
<br />12-character unique ROM id of the converter device without family id and
CRC code </li>
</ul>
<br />
<a name="OWLCDset">
<b>Set</b></a>
<ul>
<li><a name="owlcd_icon">
<code>set &lt;name&gt; icon &lt;int&gt; on|off|blink</code></a><br /> Set
one of the icons 0..14 on, off or blinking</li>
<li><a name="owlcd_icon2">
<code>set &lt;name&gt; icon 15 0..6</code></a><br /> Set icon 15 to one of
its values</li>
<li><a name="owlcd_icon3">
<code>set &lt;name&gt; icon none</code></a><br /> Set all icons off</li>
<li><a name="owlcd_line">
<code>set &lt;name&gt; line &lt;int&gt; &lt;string&gt;</code></a><br />
Write LCD line 0..3 with some content </li>
<li><a name="owlcd_memory">
<code>set &lt;name&gt; memory &lt;page&gt;
&lt;string&gt;</code></a><br />Write memory page 0..6</li>
<li><a name="owlcd_gpio">
<code>set &lt;name&gt; gpio &lt;value&gt;</code></a><br />Write state for
all three gpio pins (value = 0..7, for each bit 0=ON, 1=OFF)</li>
<li><a name="owlcd_bl">
<code>set &lt;name&gt; backlight ON|OFF</code></a><br />Switch backlight on
or off</li>
<li><a name="owlcd_lcd">
<code>set &lt;name&gt; lcd ON|OFF</code></a><br />Switch LCD power on or
off</li>
<li><a name="owlcd_gpio">
<code>set &lt;name&gt; reset</code></a><br />Reset the display</li>
<li><a name="owlcd_gpio">
<code>set &lt;name&gt; test</code></a><br />Test the display</li>
</ul>
<br />
<a name="owlcdget">
<b>Get</b></a>
<ul>
<li><a name="owlcd_id">
<code>get &lt;name&gt; id</code></a>
<br /> Returns the full 1-Wire device id OW_FAMILY.ROM_ID.CRC </li>
<li><a name="owlcd_present">
<code>get &lt;name&gt; present</code>
</a>
<br /> Returns 1 if this 1-Wire device is present, otherwise 0. </li>
<li><a name="owlcd_memory2">
<code>get &lt;name&gt; memory &lt;page&gt;</code></a><br />Read memory page
0..6 </li>
<li><a name="owlcd_gpio">
<code>get &lt;name&gt; gpio</code></a><br />Obtain state of all four input
channels (15 = all off, 0 = all on)</li>
<li><a name="owlcd_counter">
<code>get &lt;name&gt; gpio</code></a><br />Obtain state of all four input
counters (4 x 16 Bit)</li>
<li><a name="owlcd_version">
<code>get &lt;name&gt; version</code></a><br />Obtain firmware version of
the controller</li>
</ul>
<br />
<a name="owlcdattr">
<b>Attributes</b></a>
<ul>
<li>Standard attributes alias, comment, eventMap, logLevel, webCmd</li>
</ul>
</ul>
<!--+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++-->
<a name="OWSWITCH"></a>
<h3>OWSWITCH</h3>
<ul>FHEM module to commmunicate with 1-Wire Programmable Switches <br /><br /> Note:<br />
This 1-Wire module so far works only with the OWX interface module. Please define an <a
href="#OWX">OWX</a> device first. <br />
<br /><b>Example</b><br />
<ul>
<code>define OWX_S OWSWITCH DS2413 B5D502000000 60</code>
<br />
<code>attr OWX_S AName Lampe|light</code>
<br />
<code>attr OWX_S AUnit AN|AUS</code>
<br />
</ul>
<br />
<a name="OWSWITCHdefine"></a>
<b>Define</b>
<ul>
<code>define &lt;name&gt; OWSWITCH [&lt;model&gt;] &lt;id&gt;
[&lt;interval&gt;]</code>
<br /><br /> Define a 1-Wire switch.<br /><br />
<li>
<code>[&lt;model&gt;]</code><br /> Defines the switch model (and thus 1-Wire
family id), currently the following values are permitted: <ul>
<li>model DS2413 with family id 3A (default if the model parameter is
omitted)</li>
</ul>
</li>
<li>
<code>&lt;id&gt;</code>
<br />12-character unique ROM id of the converter device without family id and
CRC code </li>
<li>
<code>&lt;interval&gt;</code>
<br />Measurement interval in seconds. The default is 300 seconds. </li>
</ul>
<br />
<a name="OWSWITCHset">
<b>Set</b></a>
<ul>
<li><a name="owswitch_interval">
<code>set &lt;name&gt; interval &lt;int&gt;</code></a><br /> Measurement
interval in seconds. The default is 300 seconds. </li>
<li><a name="owswitch_output">
<code>set &lt;name&gt; output &lt;channel-name&gt; ON |
OFF</code></a><br />Switch channel on/off (A, B or named channel, see
below)</li>
<li><a name="owswitch_gpio">
<code>set &lt;name&gt; gpio &lt;value&gt;</code></a><br />Write state for
all channels (for each bit 0=ON, 1=OFF)</li>
</ul>
<br />
<a name="OWSWITCHget">
<b>Get</b></a>
<ul>
<li><a name="owswitch_id">
<code>get &lt;name&gt; id</code></a>
<br /> Returns the full 1-Wire device id OW_FAMILY.ROM_ID.CRC </li>
<li><a name="owswitch_present">
<code>get &lt;name&gt; present</code>
</a>
<br /> Returns 1 if this 1-Wire device is present, otherwise 0. </li>
<li><a name="owswitch_interval2">
<code>get &lt;name&gt; interval</code></a><br />Returns measurement interval
in seconds. </li>
<li><a name="owswitch_input">
<code>get &lt;name&gt; INPUT &lt;channel-name&gt;</code></a><br />Obtain
state of channel (A, B or named channel, see below)</li>
<li><a name="owswitch_gpio">
<code>get &lt;name&gt; gpio</code></a><br />Obtain state of all
channels</li>
</ul>
<br />
<a name="OWSWITCHattr">
<b>Attributes</b></a> For each of the following attributes, the channel
identification A,B may be used. <ul>
<li><a name="owswitch_cname"><code>attr &lt;name&gt; &lt;channel&gt;Name
&lt;string&gt;|&lt;string&gt;</code></a>
<br />name for the channel | a type description for the measured value. </li>
<li><a name="owswitch_cunit"><code>attr &lt;name&gt; &lt;channel&gt;Unit
&lt;string&gt;|&lt;string&gt;</code></a>
<br />display for on | off condition </li>
<li>Standard attributes alias, comment, eventMap, logLevel, webCmd</li>
</ul>
</ul>
<!--+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++-->
<a name="OWTHERM"></a>
<h3>OWTHERM</h3>
<ul>FHEM module to commmunicate with 1-Wire bus digital thermometer devices<br /><br />
Note:<br /> This is the only 1-Wire module which so far works with both the OWFS and the
OWX interface module. Please define an <a href="#OWFS">OWFS</a> device or an <a
href="#OWX">OWX</a> device first. <br />
<br /><b>Example</b><br />
<ul>
<code>define OWX_T OWTHERM DS18B20 E8D09B030000 300</code>
<br />
<code>attr OWX_T tempUnit Kelvin</code>
<br />
</ul><br />
<a name="OWTHERMdefine"></a>
<b>Define</b>
<ul>
<code>define &lt;name&gt; OWTHERM [&lt;model&gt;] &lt;id&gt;
[&lt;interval&gt;]</code>
<br /><br /> Define a 1-Wire digital thermometer device.<br /><br />
<li>
<code>[&lt;model&gt;]</code><br /> Defines the thermometer model (and thus
1-Wire family id) currently the following values are permitted: <ul>
<li>model DS1820 with family id 10 (default if the model parameter is
omitted)</li>
<li>model DS1822 with family id 22</li>
<li>model DS18B20 with family id 28</li>
</ul>
</li>
<li>
<code>&lt;id&gt;</code>
<br />12-character unique ROM id of the thermometer device without family id and
CRC code </li>
<li>
<code>&lt;interval&gt;</code>
<br /> Temperature measurement interval in seconds. The default is 300 seconds. </li>
<br /> Example: <br />
<code>define Temp1 OWTHERM 14B598010800 300 </code><br />
</ul>
<br />
<a name="OWTHERMset">
<b>Set</b></a>
<ul>
<li><a name="owtherm_interval">
<code>set &lt;name&gt; interval &lt;int&gt;</code></a><br /> Temperature
measurement intervall in seconds. The default is 300 seconds.</li>
<li><a name="owtherm_tempHigh">
<code>set &lt;name&gt; tempHigh &lt;float&gt;</code></a>
<br /> The high alarm temperature (on the temperature scale chosen by the
attribute value) </li>
<li><a name="owtherm_tempLow">
<code>set &lt;name&gt; tempLow &lt;float&gt;</code></a>
<br /> The low alarm temperature (on the temperature scale chosen by the
attribute value) </li>
</ul>
<br />
<a name="OWTHERMget">
<b>Get</b></a>
<ul>
<li><a name="owtherm_id">
<code>get &lt;name&gt; id</code></a>
<br /> Returns the full 1-Wire device id OW_FAMILY.ROM_ID.CRC </li>
<li><a name="owtherm_present">
<code>get &lt;name&gt; present</code></a>
<br /> Returns 1 if this 1-Wire device is present, otherwise 0. </li>
<li><a name="owtherm_interval2">
<code>get &lt;name&gt; interval</code></a><br />Returns temperature
measurement interval in seconds.</li>
<li><a name="owtherm_temperature">
<code>get &lt;name&gt; temperature</code></a><br />Obtain the temperature. </li>
<li><a name="owtherm_alarm">
<code>get &lt;name&gt; alarm</code></a><br />Obtain the alarm temperature
values. </li>
</ul>
<br />
<a name="OWTHERMattr">
<b>Attributes</b></a>
<ul>
<li><a name="owtherm_stateAL"><code>attr &lt;name&gt; stateAL &lt;string&gt;</code>
</a>
<br />character string for denoting low alarm condition, default is red down
triangle, e.g. the code &lt;span style="color:red"&gt;&amp;#x25BE;&lt;/span&gt;
leading to the sign <span style="color:red">&#x25BE;</span>
</li>
<li><a name="owtherm_stateAH"><code>attr &lt;name&gt; stateAH &lt;string&gt;</code>
</a>
<br />character string for denoting high alarm condition, default is red upward
triangle, e.g. the code &lt;span style="color:red"&gt;&amp;#x25B4;&lt;/span&gt;
leading to the sign <span style="color:red">&#x25B4;</span>
</li>
<li><a name="owtherm_tempOffset"><code>attr &lt;name&gt; tempOffset
&lt;float&gt;</code>
</a>
<br />temperature offset in &deg;C added to the raw temperature reading. </li>
<li><a name="owtherm_tempUnit"><code>attr &lt;name&gt; tempUnit
Celsius|Kelvin|Fahrenheit|C|K|F</code>
</a>
<br />unit of measurement (temperature scale), default is Celsius = &deg;C </li>
<li><a name="owtherm_tempHigh2">
<code>attr &lt;name&gt; tempHigh &lt;float&gt;</code>
</a>
<br /> high alarm temperature (on the temperature scale chosen by the attribute
value). </li>
<li><a name="owtherm_tempLow2">
<code>attr &lt;name&gt; tempLow &lt;float&gt;</code>
</a>
<br /> low alarm temperature (on the temperature scale chosen by the attribute
value). </li>
<li>Standard attributes alias, comment, eventMap, logLevel, webCmd</li>
</ul>