10_EnOcean: Generic Profiles supported

git-svn-id: https://svn.fhem.de/fhem/trunk@9225 2b470e98-0d58-463d-a4d8-8e2adae1ed80
This commit is contained in:
klaus-schauer 2015-09-10 18:09:09 +00:00
parent 51897ce19b
commit d45cfb6023

View File

@ -11298,7 +11298,7 @@ EnOcean_Undef($$)
<a href="#setExtensions">set extensions</a> are supported, if the corresponding
<a href="#eventMap">eventMap</a> specifies the <code>on</code> and <code>off</code>
mappings, for example <code>attr <name> eventMap on-till:on-till AI:on A0:off</code>.<br>
If <a href="#comMode">comMode</a> is set to biDir the device can be controlled bidirectionally.<br>
If <a href="#EnOcean_comMode">comMode</a> is set to biDir the device can be controlled bidirectionally.<br>
With the help of additional <a href="#EnOceanattr">attributes</a>, the behavior of the devices can be adapt.<br>
The attr subType must be switch.00. This is done if the device was created by autocreate.
<br><br>
@ -12074,14 +12074,39 @@ EnOcean_Undef($$)
<li>teachOut<br>
initiate UTE teach-out (slave)</li>
</ul><br>
The valve controller is configured using the following attributes:<br>
The generic profile device is configured using the following attributes:<br>
<ul>
<li><a href="#EnOcean_comMode">comMode</a></li>
<li><a href="#EnOcean_devMode">devMode</a></li>
<li><a href="#EnOcean_gpDef">gpDef</a></li>
<li><a href="#EnOcean_manufID">manufID</a></li>
</ul>
The attr subType must be valveCtrl.00. This is done if the device was
created by autocreate. To control the device, it must be bidirectional paired,
see <a href="#EnOcean_teach-in">Bidirectional Teach-In / Teach-Out</a>. The profile
behaves like a master or slave, see <a href="#EnOcean_devMode">devMode</a>.
The attr subType must be genericProfile. This is done if the device was
created by autocreate. If the profile in slave mode is operated, especially the channel
definition in the gpDef attributes must be entered manually.
</li>
<br><br>
<li>Generic Profiles<br>
<ul>
<code>set &lt;name&gt; &lt;value&gt;</code>
<br><br>
where <code>value</code> is
<li>&lt;00 ... 64&gt;-&lt;channel name&gt; &lt;value&gt;<br>
set channel value</li>
<li>channelName &lt;channel number&gt;-&lt;channel name&gt;<br>
rename channel</li>
<li>teachIn<br>
sent teach-in telegram</li>
<li>teachOut<br>
sent teach-out telegram</li>
</ul><br>
[data] = &lt;1-byte hex ... 512-byte hex&gt;<br>
[status] = 0x00 ... 0xFF<br>
With the help of this command data messages in hexadecimal format can be sent.
Telegram types (RORG) 1BS, 4BS, RPS, MSC, UTE, VLD, GPCD, GPSD, GPTI and GPTR are supported.
For further information, see <a href="http://www.enocean-alliance.org/eep/">EnOcean Equipment Profiles (EEP)</a> and
Generic Profiles.
</li>
<br><br>
@ -12273,7 +12298,7 @@ EnOcean_Undef($$)
If the structure of the MSC telegrams can not interpret the raw data to be output. Setting this attribute to yes,
the output can be suppressed.
</li>
<li><a name="comMode">comMode</a> biDir|confirm|uniDir, [comMode] = uniDir is default.<br>
<li><a name="EnOcean_comMode">comMode</a> biDir|confirm|uniDir, [comMode] = uniDir is default.<br>
Communication Mode between an enabled EnOcean device and Fhem.<br>
Unidirectional communication means a point-to-multipoint communication
relationship. The EnOcean device e. g. sensors does not know the unique
@ -12368,12 +12393,24 @@ EnOcean_Undef($$)
</li>
<li><a href="#do_not_notify">do_not_notify</a></li>
<li><a href="#eventMap">eventMap</a></li>
<li><a name="EnOcean_eep">eep</a> [00...FF].[00...3F].[00...7F]<br>
<li><a name="EnOcean_eep">eep</a> &lt;00...FF&gt;-&lt;00...3F&gt;-&lt;00...7F&gt;<br>
EnOcean Equipment Profile (EEP)
</li>
</li>
<li><a name="EnOcean_gpDef">gpDef</a> &lt;name of channel 00&gt;:&lt;O|I&gt;:&lt;channel type&gt;:
&lt;signal type&gt;:&lt;value type&gt;[[:&lt;resolution&gt;]
[:&lt;engineering min&gt;:&lt;scaling min&gt;:&lt;engineering max&gt;:&lt;scaling max&gt;]] ...
&lt;name of channel 64&gt;:&lt;O|I&gt;:&lt;channel type&gt;:
&lt;signal type&gt;:&lt;value type&gt;[[:&lt;resolution&gt;]
[:&lt;engineering min&gt;:&lt;scaling min&gt;:&lt;engineering max&gt;:&lt;scaling max&gt;]]
<br>
Generic Profiles channel definitions are set automatically in master mode. If the profile in slave mode is operated, the channel
definition must be entered manually. For each channel, the channel definitions are to be given in ascending order. The channel
parameters to be specified in decimal. First, the outgoing channels (direction = O) are to be defined, then the incoming channels
(direction = I) should be described. The channel numbers are assigned automatically starting with 00th.
</li>
<li><a name="gwCmd">gwCmd</a> switching|dimming|setpointShift|setpointBasic|controlVar|fanStage|blindCmd<br>
Gateway Command Type, see <a href="#Gateway">Gateway</a> profile
</li>
</li>
<li><a name="EnOcean_humidity">humidity</a> t/&#176C<br>
The value of the actual humidity, used by a Room Sensor and Control Unit. Should by
filled via a notify from a distinct humidity sensor.
@ -12393,6 +12430,9 @@ EnOcean_Undef($$)
<li><a name="EnOcean_macAlgo">macAlgo</a> no|3|4<br>
MAC Algorithm
</li>
<li><a name="EnOcean_manufID">manufID</a> &lt;000 ... 7FF&gt;<br>
Manufacturer ID number
</li>
<li><a href="#model">model</a></li>
<li><a name="EnOcean_observe">observe</a> off|on, [observe] = off is default.<br>
Observing and repeating the execution of set commands
@ -14028,6 +14068,20 @@ EnOcean_Undef($$)
</li>
<br><br>
<li>Generic Profiles<br>
<ul>
<li>&lt;00...64&gt;-&lt;channel name&gt; &lt;value&gt;</li>
<li>&lt;00...64&gt;-&lt;channel name&gt;Unit &lt;value&gt;</li>
<li>&lt;00...64&gt;-&lt;channel name&gt;ValueType value|setpointAbs|setpointRel</li>
<li>&lt;00...64&gt;-&lt;channel name&gt;ChannelType teachIn|data|flag|enum</li>
<li>teach &lt;value&gt;</li>
</ul><br>
The attr subType must be genericProfile. This is done if the device was
created by autocreate. If the profile in slave mode is operated, especially the channel
definition in the gpDef attributes must be entered manually.
</li>
<br><br>
<li>RAW Command<br>
<ul>
<li>RORG: 1BS|4BS|MCS|RPS|UTE|VLD</li>